N2XRY Copper Conductor SWA 600/1000V Cable,CU/XLPE/SWA/PVC

0.6/1kV N2XRY Cable, CU/XLPE/SWA/PVC

Application:

· Power and auxiliary fixed wiring cables

· Power networks

· Underground

· Outdoor and indoor devices

 

Voltage Rating (Uo/U) : 0.6/1K 

Temperature Rating Fixed: -25°C to +90°C   

For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)

Share:

Details

CU/XLPE/SWA/PVC Cable  

CU/XLPE/SWA/PVC Armoured Power Cables are the perfect choice when you need the toughest and most durable armoured cable for power distribution and transmission. Made with a layer of steel wire armoured (SWA), polyethylene (XLPE) thermosetting insulation, and hard-wearing PVC, these armoured cables can withstand twisting, crushing, impacts, temperature extremes, moisture, chemical hazards, and more. They’re suitable for use in a range of environments, from industrial and manufacturing facilities to construction  

Construction

N2XRY Copper Conductor SWA 600/1000V Cable,CU/XLPE/SWA/PVC

Description: N2XRY, XLPE Insulated Copper Power Cable   

Conductors:Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.

Insulation:Cross-linked polyethylene XLPE

Insulation Colour:Natural or as required

Filler: Non-hygroscopic Material

Inner Sheath: Polyvinyl Chloride PVC

Reinforcement: Steel Wire
Outer SheathExtruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath:  Black
Voltage Rating (Uo/U): 600/1000V   
Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-3+1 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
3X4+1X2.50.7/0.71.251.817.88734.61/7.4126 36 
3X6+1X40.7/0.71.251.819.17643.08/4.6133 45 
3X10+1X60.7/0.71.251.821.610021.83/3.0846 60 
3X16+1X100.7/0.71.61.825.114751.15/1.8359 77 
3X25+1X160.9/0.71.61.828.721010.727/1.1577 98 
3X35+1X160.9/0.71.61.83023000.524/1.1595 119
3X50+1X251/0.91.6234.129450.387/0.727119 144 
3X70+1X351.1/0.922.139.241310.268/0.524151 175 
3X95+1X501.1/1.022.343.251990.193/0.387186 210 
3X120+1X701.2/1.12.52.448.868270.153/0.268217 242 
3X150+1X701.4/1.12.52.652.979150.124/0.268245 270 
3X185+1X951.6/1.12.52.757.896550.0991/0.193284 305 
3X240+1X1201.7/1.22.52.964.1119880.0754/0.153336 350 
3X300+1X1501.8/1.42.53.169.8144750.0601/0.124389 396 









0.6/1kV-4+1 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
4X4+1X2.50.7/0.71.251.818.97314.61/7.4126 36 
4X6+1X40.7/0.71.251.820.38753.08/4.6133 45 
4X10+1X60.7/0.71.61.823.912951.83/3.0846 60 
4X16+1X100.7/0.71.61.82717121.15/1.8359 77 
4X25+1X160.9/0.71.61.931.223220.727/1.1577 98 
4X35+1X160.9/0.71.61.932.827590.524/1.1595 119
4X50+1X251/0.922.138.538600.387/0.727119 144 
4X70+1X351.1/0.922.34350100.268/0.524151 175 
4X95+1X501.1/1.02.52.448.968500.193/0.387186 210 
4X120+1X701.2/1.12.52.65483950.153/0.268217 242 
4X150+1X701.4/1.12.52.758.497450.124/0.268245 270 
4X185+1X951.6/1.12.52.964.4119480.0991/0.193284 305 
4X240+1X1201.7/1.22.53.171.1148320.0754/0.153336 350 
4X300+1X1501.8/1.43.153.478.9188260.0601/0.124389 396 









0.6/1kV-3+2 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
3X4+2X2.50.7/0.71.251.818.67054.61/7.4126 36 
3X6+2X40.7/0.71.251.8208453.08/4.6133 45 
3X10+2X60.7/0.71.251.822.511091.83/3.0846 60 
3X16+2X100.7/0.71.61.826.516301.15/1.8359 77 
3X25+2X160.9/0.71.61.830.221850.727/1.1577 98 
3X35+2X160.9/0.71.61.931.325050.524/1.1595 119
3X50+2X251/0.922.13735310.387/0.727119 144 
3X70+2X351.1/0.922.241.145720.268/0.524151 175 
3X95+2X501.1/1.022.445.858410.193/0.387186 210 
3X120+2X701.2/1.12.52.652.177650.153/0.268217 242 
3X150+2X701.4/1.12.52.755.487580.124/0.268245 270 
3X185+2X951.6/1.12.52.860.8107770.0991/0.193284 305 
3X240+2X1201.7/1.22.5367.4133850.0754/0.153336 350 
3X300+2X1501.8/1.42.53.273.6161000.0601/0.124389 396